Design and research
Engineering
Gas-using equipment
Testing and Certification
of Gas-Using Equipment
Gas-using Equipment List
|
MIXING AIR HEATERS
Purpose
Mixing gas air heaters of VGS type are designed for heating the atmospheric air by mixing heated environment with exhaust products.
Air heaters are used in air heating input ventilation systems and air heat curtains for industrial premises of various purposes.
VGS can be used at workshops of automotive and machine building industries, at metallurgic plants, shipbuilding and aircraft manufacturing enterprises, large warehouse facilities and agricultural objects-elevators, green houses etc.
VGS are used in drying chambers for construction materials production.
Since VGS are built in the existing air compressing system, fans and diffusers are not included into supply.
If needed, fans and diffusers can be supplied for an additional charge. Air heaters are manufactured in right-hand and left-hand types, depending on the gas input location.
Specifications
| Unit type |
VGS-0.15 |
VGS-0.4 |
VGS-0.7 |
VGS-1.0 |
VGS-1.6 |
VGS-2.0 |
VGS-2.6 |
VGS-6.3 |
VGS-0.7G |
VGS-1.0G |
| Rated heat output, MW |
0.15 |
0.4 |
0.7 |
1 |
1.6 |
2 |
2.6 |
6.3 |
0.7 |
1 |
| Rated gas consumption , m3/h |
15 |
40 |
70 |
100 |
160 |
200 |
260 |
630 |
70 |
100 |
| Heated air volume, thousand m3/h |
7.5 |
20 |
34 |
50 |
74 |
90 |
100 |
250 |
10 |
9.7 |
| Heat difference at the input and output from VGS, oС |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
30-80 |
190 |
300 |
Joint gas pressure:
|
|
|
|
|
|
|
|
|
|
|
| average, (kPa) |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
low, (kPa)
|
2 |
2.0-4.5 |
4.5 |
4.5 |
|
|
|
|
4.5 |
4.5 |
| Overall dimensions of the unit (without diffuser and fan), mm |
|
|
|
|
|
|
|
|
|
|
| length |
1,300 |
1,300 |
1,300 |
1,300 |
1,300 |
1,300 |
1,300 |
2,250 |
1,300 |
1,300 |
| width |
800 |
960 |
1,410 |
1,900 |
2,100 |
2,100 |
2,400 |
3,500 |
1,410 |
1,900 |
height
|
800 |
860 |
1,230 |
1,520 |
1,900 |
2,470 |
2,450 |
4,170 |
1,230 |
1,520 |
| Weight of the unit without diffuser, kg |
76 |
241 |
172 |
285 |
462 |
605 |
665 |
1845 |
494 |
600 |
Home
|